Overview of several control methods for all-steel fume hood variable air volume butterfly valves
single-channel all-steel fume hood variable air volume butterfly valve control:
1, using SM6 surface wind speed sensor, real-time measurement of equipment surface wind speed, feedback control of the fume hood exhaust valve;
2, to maintain a constant wind speed on the equipment surface, the system response time is <3 seconds.
1 uses SM6 surface wind speed sensor and SM2 displacement sensor to simultaneously detect the adjustment window displacement and real-time surface wind speed;
2. Quick response control through displacement measurement, within <2 seconds;
3. Adjust the precision high-pressure independent butterfly valve to the preset exhaust volume position;
4. After the adjustment window stabilizes (Boost Duration can be set, such as 3 seconds), switch to face air speed control to deal with equipment turbulence and maintain the leakage rate of the fume hood;
5, system response time <2 seconds.
adaptive all-steel fume hood variable air volume butterfly valve control:
1. Use SM10 area status sensor to detect whether there is an operator in front of the equipment;
2. When there are no operators in front of the equipment, reduce the surface wind speed setting of the fume hood to 0.3m/s. Once someone is detected, quickly adjust the surface wind speed to 0.5m/s;
3. Significantly reduce equipment energy consumption.